SCANNER & DATALOGGER

UT-30XX

  • MULTI CHANNEL INDICATOR & CONTROLLER

     

    ♦ Microprocessor Based Powerful & Highly Reliable Process Display.

    ♦ 4 , 8, 12, 16, 24 Channel Display With Data Logger Available.

    ♦ All Input Are Universal Like T/C, RTD Linear Selection.

    ♦ 0.1 % Accuracy Of FSD.

    ♦ All Channels Are Fully Isolated.

    ♦ All Configurations And Calibration From Front Panel Keypad.

    ♦ High Speed Serial RS-232 / 485 Comm. For On Line Data Logging.

    ♦ Transmitter Loop Power Supply With Current Limit As Standard.

    ♦ Power Supply :230 V/110 V AC. Or 24 V/12 V DC.

    ♦ Optional GSM Mobile Connectivity.

  •  FEATURE

     

    ♦ Microprocessor based powerful & highly reliable process display.

    ♦ 4/6/8/12/16/20/24 channel option available.

    ♦ All input are universal like T/C, RTD, linear selection.

    ♦ Simultaneously display for individual channel in compact size.

    ♦ All channels are fully Isolated.

    ♦ All Configurations and calibration from front panel keypad.

    ♦ High speed communicative serial (RS 232/485) interface.

    ♦ Transmitter loop power supply with current limit as standard.

    ♦ Power supply : 230V/110V AC or 24V/12V DC

INPUT Input Type For 4,8,12,16 Channel Instruments T/C K, J, R, S, E, N, T
RTD PT-100, Cu53 ( 2wire & 3 wire)
Current 0 ~ 20 mA DC, 4~20 mA DC
Voltage 0-5 V,1-5 V, 0.5 -2.5 V,0- 10 V DC
Transmitter Power Supply 24 V DC @ 30 mA Max, Isolated From I/P & O/P
Cold Junction Comp. & Sensor Break Ind. Software Base Automatic
OUTPUT Range Limits As Per Input Range Table
Accuracy +/- 0.1 % of Span For Linear & RTD, +/-0.25 % For T/C
Input Impedance >330 K for Voltage ,mV, And T/C, 100 R For Current
INDICATION Indication 4, 8, 12,16 Indicator Seven Segment All Chanel Are Independent 4 Digit.
Status Indication LEDs For Relay Status & Communication
Alarm Modes Very Low/Low/High/Very High
FLAME PROOF Gas Group I, IIA , IIB, IIC, as per IS 2148/1981 -
Enclose Certification Enclosure Is Certified By C.M.R.I. CCOE
Relay Output NO - C - NC Contacts , 5A @ 240 V AC Resistive
SSR Output 1 / 2 / 3 / 4 Relays / SSR Output Per Channel Relay.
Transmitter Power 24 V DC @ 20 mA ,12 V DC @ 20 mA DC
COMMUNICATION Communication Protocol & Method Modbus RTU RS- 485/ Ethernet TCP-IP & Wi-Fi , Bluetooth , USB
Programmable Parameter & Max No. Baud Rate, Parity , Node Address , Stop Bit & 0-256 Unit IP Add
Wireless Communication RF 2 KM / GPRS Base Mobile(sms) Communication
PROGRAMMBALE PARAMETERS Set point / High Scale / Low Scale/ Node Id Full Range As Per input Selection
Relay Logic F.S. High & Low Alarm, Dead Band Alarm
Display Resolution -1999 to 9999 Fully Configurable For Linear Input
Programming Of Parameters Touch Screen. Or Through 5 To Tactile Keys
OTHER Dimensions & Mounting As Per Box Selection & Wall/Structure 2/2 Holes
(A) Supply Voltage (B) Power Consumption (A) 110/230 AC/24VDC, 50/60 Hz (B) 4 Watts Maximum
Operating Ambient Temperature And Humidity 0~50 °C , And Humidity : Below 90%, Non Condensing