SIGNAL ISOLATOR CUM MULTIPLEXER
♦ Microprocessor Based Highly Reliable Isolator With Slim And Compact Design (22.5 mm & 35 mm).
♦ Universal Input T/C, RTD, Linear Input Selection.
♦ Mutual Isolation Between Input, Output1, Output2 And Power Supply.
♦ 0.1% Accuracy Of FS. (Din Rail Mounting).
♦ Supplemented With 1, 2, 3, 4 Isolated 4-20 mA DC Outputs For One Input Option.
♦ All Configurations And Calibration From Windows Base Software Utility
♦ Modbus RS-485 Highly Communicative Serial Interface Facility.
♦ Transmitter Loop Power Supply With Current Limit As Standard.
♦ Optional Input Like AC/DC Volt, AC/DC Current, milliamp, millivolt, Frequency Or Load Cell Inputs Available.
♦ μP Based Slim & compact design (45.5 mm width).
♦ Supplemented with 1, 2, 3, 4 isolated outputs for one input option.
♦ Input milliamp, millivolt, RTD, Thermocouple.
♦ High bright 4 Led seven segments display in din rail housing.
♦ 1.5 KV 3 Port Isolation & 0.25% Accuracy of FSD.
♦ All Configurations and calibration from front panel keypad.
♦ loop power supply with current limit as standard.
INPUT | Input Type | T/C | K, J, R, S, E, N, T |
RTD | Pt-100, Cu 53 ( 2wire & 3 wire) | ||
Current | 0 ~ 20 mA DC, 4~20 mA DC 0-1/5 AMP. AC | ||
Voltage | 0-5 V/1-5 V, 0.5 -2.5 V/0- 10 V DC | ||
Special on demand | 0-75/200 mV & 0-1/10V/100/300 V AC/DC | ||
Resistance : | 0-75/200 mV 0-100/300 V DC && 0-500 R , 0-1/5/10 K, 1M | ||
Transmitter Power Supply | 24 V DC @ 30 mA Max, Isolated From I/P & O/P | ||
Cold Junction Comp. & Sensor Break Ind. | Software Base Automatic | ||
Response Time | 1 Ms to 200 Ms Default-200 Ms | ||
Accuracy | +/- 0.1 % Of Span For Linear & RTD, +/-0.25 % For T/C | ||
Input Impedance | >330 K For Voltage ,mV, And T/C, 100 R For Current | ||
ISOLATION | Input - 1.5 KVA Between) | Input to Power & Input To Output | |
Power - 1.5 KVA Between | Power To Input & Power To Output | ||
Output- 1.5 KVA Between | Output To Power & Output To Output & Output To Input | ||
COMMUNICATION | Communication Protocol & Method | Modbus RTU RS- 485/RS- 232 Communication | |
Programmable Parameter & Max No. | Baud Rate, Parity , Node Address , Stop Bit & 0-256 Unit | ||
OUTPUT | Output Type | 4-20 mA DC , 0-20 mA DC , 0-10 V DC , 0-1/2/5 V DC | |
Nos. Of Output | 1,2,3,4 All Are Isolated | ||
OTHER | Dimensions & Mounting | (A) 110,230 AC & 24 VDC, 50/60 Hz (B) 4 Watts Maximum | |
Operating Ambient Temperature And Humidity | 0~50 °C , And Humidity : Below 90%, Non Condensing |