SIGNAL ISOLATOR

UT-1102

  • SIGNAL ISOLATOR CUM MULTIPLEXER

     

    ♦ Microprocessor Based Highly Reliable Isolator With Slim And Compact Design (22.5 mm & 35 mm).

    ♦ Universal Input T/C, RTD, Linear Input Selection.

    ♦ Mutual Isolation Between Input, Output1, Output2 And Power Supply.

    ♦ 0.1% Accuracy Of FS. (Din Rail Mounting).

    ♦ Supplemented With 1, 2, 3, 4 Isolated 4-20 mA DC Outputs For One Input Option.

    ♦ All Configurations And Calibration From Windows Base Software Utility

    ♦ Modbus RS-485 Highly Communicative Serial Interface Facility.

    ♦ Transmitter Loop Power Supply With Current Limit As Standard.

    ♦ Optional Input Like AC/DC Volt, AC/DC Current, milliamp, millivolt, Frequency Or Load Cell Inputs Available.

  •  FEATURE

     

    ♦ μP Based Slim & compact design (45.5 mm width).

    ♦ Supplemented with 1, 2, 3, 4 isolated outputs for one input option.

    ♦ Input milliamp, millivolt, RTD, Thermocouple.

    ♦ High bright 4 Led seven segments display in din rail housing.

    ♦ 1.5 KV 3 Port Isolation & 0.25% Accuracy of FSD.

    ♦ All Configurations and calibration from front panel keypad.

    ♦ loop power supply with current limit as standard.

INPUT Input Type T/C K, J, R, S, E, N, T
RTD Pt-100, Cu 53 ( 2wire & 3 wire)
Current 0 ~ 20 mA DC, 4~20 mA DC 0-1/5 AMP. AC
Voltage 0-5 V/1-5 V, 0.5 -2.5 V/0- 10 V DC
Special on demand 0-75/200 mV & 0-1/10V/100/300 V AC/DC
Resistance : 0-75/200 mV 0-100/300 V DC && 0-500 R , 0-1/5/10 K, 1M
Transmitter Power Supply 24 V DC @ 30 mA Max, Isolated From I/P & O/P
Cold Junction Comp. & Sensor Break Ind. Software Base Automatic
Response Time 1 Ms to 200 Ms Default-200 Ms
Accuracy +/- 0.1 % Of Span For Linear & RTD, +/-0.25 % For T/C
Input Impedance >330 K For Voltage ,mV, And T/C, 100 R For Current
ISOLATION Input - 1.5 KVA Between) Input to Power & Input To Output
Power - 1.5 KVA Between Power To Input & Power To Output
Output- 1.5 KVA Between Output To Power & Output To Output & Output To Input
COMMUNICATION Communication Protocol & Method Modbus RTU RS- 485/RS- 232 Communication
Programmable Parameter & Max No. Baud Rate, Parity , Node Address , Stop Bit & 0-256 Unit
OUTPUT Output Type 4-20 mA DC , 0-20 mA DC , 0-10 V DC , 0-1/2/5 V DC
Nos. Of Output 1,2,3,4 All Are Isolated
OTHER Dimensions & Mounting (A) 110,230 AC & 24 VDC, 50/60 Hz (B) 4 Watts Maximum
Operating Ambient Temperature And Humidity 0~50 °C , And Humidity : Below 90%, Non Condensing